Front Panel Sealing | NEMA 3 / IP66 |
---|---|
Temperature Stability | 0.01 % of span per ºC |
Accuracy | 0.1 % of span ± 1 LSD |
Alarms | Maximum number of alarms: 2 soft alarms setpoint + 1 loop alarm |
Power Consumption | 4 W |
Input Signal Failure | Fail-safe output value: Achieved when burnout is detected. Value depends on configuration. For thermocouple and mV input detected by any lead break: Upscale burnout. For RTD: Burnout detected by any lead break. Current or voltage input: Burnout set by ope |
Approvals | UL, FM approval on the UDC1200 Limit Model |
Operative Frequency | 50 - 60 HZ |
Source Resistance | 1000 ohms maximum for thermocouple |
Approvals | UL , FM |